Products & Services

> </div>
<div class=

Detuned Reactor

APPLICATIONS:
POWER FACTOR PANELS
FURNACE PANELS
UPS
FLUROSCENT LAMPS

Om make reactors are designed to meet specific design criteria such as Q factor, inductance tolerances etc. series line reactors shall be designed for harmonic filtering service and for slowing the rate of rapid current charges. The reactors shall be UL component - recognized and shall be built to comply to UL 508 construction shall be of copper wire - wound on magnetic steel cores. Series line reactors shall be sized appropriately for the total connected load. Design maximum temperature rise for reactors shall be 115°c on bobbin wound and 155°c on form wound devices at rated circuit.
Non-linear equipment generate harmonic as multiples of a fundamental frequency such as AC/DC motor speed controllers, are furnaces compact fluorescent lamps, uninterruptible power sources. As a result of this fact besides the fundamental frequency, 3rd, 5th, 7th, 9th, 13th, harmonic are generated.
Specification of Harmonic filter Reactor (Detuned Reactor) 
1. Operating Voltage: 3 x 415/440V
2. Supply Frequency: 50/60Hz 
3. Filtering Detuning Factor: 5.69%, 7%, 14% corresponding to tuning frequencies of 210Hz, 189Hz, and 134 Hz for the base of 50Hz.
4. Tolerance of Inductance: ± 5%
5. High Linearity: 1.8In (180% )
6. Over Load Capability: 150 % for 10 minute of Rated current & 200 % 10 Second of Rated current
7. Insulation Class: 'F' & 'H'
8. High Voltage Test: 4 KVA
9. Temperature rise: 110° < maximum on full Load
10. Maximum Audible Level at Two (2) Meters : Line / Load Application 76 dBa 
11. Standard: IS-5553-/EN-61558-2-20/IEC-60076-6
12. 'CE' approved & UL recognized components class IEIS File E 318161.

PRODUCT RANGE:
5KVAr to 100 KVAr(Copper/Aluminum)

 
Ac And Dc Drive Applied Harmonic Filter * Ac And Dc Drive Applied Harmonic Filter (Omhg7) * Auto Wound Transformer * Control Transformer * Control Transformers * Current Transformers * Detuned Reactor (Series Reactor) * Digital Servo Voltage Stabilizers * Distribution Transformer * Distribution Transformers * Double Wound Transformer * Dry Type Transformer * Dynamic Braking Resistor * Electrical Power Transformer * Electrical Transformer * Furnace Transformer * Furnace Transformers * Hand Lamp And Portable Safety Transformers * High Voltage Transformers * Industrial Transformers * Isolation Transformers * K Rated Transformers * Lighting Transformers * Line Choke And Reactor * Load Bank Resistive And Inductive * Low Voltage Transformers * Manual Voltage Stabilizers * Oil Cooled Servo Voltage Stabilizers * Oil Transformers * Power Distribution Transformers * Power Transformers * Servo Controlled Stabilizers * Servo Stabilizer * Single Phase Transformer * Special Purpose Transformer * Stabilizers * Step Down Furnace Transformers * Three Phase To Single Phase Transformer * Three Phase Transformer * Transformers * Ultra Isolation Transformer * Ultra Isolation Transformers * Variable Transformer * Voltage Stabilizers * Voltage Transformer * Welding Transformers * Electrical Transformers (Mfgrs. And Dealers) * Potential Transformers * Transformers (Mfgrs And Dealers) * Servo Voltage Stabilizers